3.2.1 Tender OP Laminar outlet for operating theaters ... Unit Air outlet for the supply of sterile air to the operating zone using the laminar flow principle, consisting of: Housing __ without lighting throughfeed, __ with throughfeed for surgical lighting at customer’s expense. Air discharge element with fine-meshed fabric for laminar displacement flow. Air-tight filter housing to accommodate filter cells, with built-in sealing frame and surrounding test groove to DIN 1946, Part 4, Connection for leakage detector and measurement point for pressure differential and particle sampling on the untreated air side. Anschluss-Stutzen rechteckig, Rectangular connection spigot, __ with air-tight shutoff dampers to DIN 1946, Part 4 including __ electrical spring-return motor. HEPA filter cells, Filter class H14, DIN EN 1822-1. __ Built-in lighting *2). __ Surrounding lighting *2). Technical data: Volume flow rate: ... l/s (m3/h) Perm. sound power level: ... dB(A) ref. 10-12 W Total pressure loss for uncontaminated filter cell: ... Pa Materials Air outlet housing: Stainless steel, 1.4301 Filter housing: __ Galvanized steel with powder coating *3) Air outlet frame: Stainless steel 1.4301 Air discharge element (laminar fabric): Polyester Ceiling connection profile: Stainless steel, 1.4301 Air-tight shutoff dampers: Galvanized steel Dimensions: Air outlet housing A x B: ... mm x ... mm Total height: ... mm Filter cells: ... mm x ... mm Make: KRANTZ KOMPONENTEN Type: OP Subject to technical alterations! ------------------------------------------------- *2) On request *3) Stainless steel on request YIT Germany GmbH KRANTZ KOMPONENTEN Uersfeld 24 | D-52072 Aachen | Germany Phone: +49 241 441-1 | Fax: +49 241 441-555 info@krantz.de | www.krantz.de