Tender text Puridrall, type PDV and Puri inlet, type PEV ---------------------------------------------------------------- 3.1.2 Tender text Puridrall, type PDV ... units Puridrall, air outlet for clean rooms with twist outlet for turbulent mixing air flow and pronounced induction effect between supply air and indoor air, easily detachable from room, suitable for clean rooms of classes 6 to 8 to DIN EN ISO 14644-1 or 1 000 to 100 000 to US Federal Standard 209 as well as C and D to EG-GMP, filter housing air-tight to DIN 25414, including sealing frame for dry sealing with surrounding test groove for tightness test to DIN 1946, Part 4, contact pressure fixture for filter cell, replacement filter cell from below Air connection with __ rectangular connection flange, lateral, __ circular connection spigot, __ lateral, __ on top, Measurement point for pressure differential as well as particle sampling on the untreated air side. HEPA filter cell with cell frame, including dry sealing. Technical data: Volume flow rate: ... l/s (m3/h) Filter class: __ H13; __ H14 *1) Perm. sound power level: ... dB(A) ref. 10-12 W Total pressure loss with uncontaminated filter cell: ... Pa Materials: Filter housing, sealing frame and twist outlet: Galvanized sheet metal Surface protection: Epoxy polyester resin coating, disinfectant-proof Connection housing: Galvanized sheet metal __ Surface protection: Epoxy polyester resin coating, disinfectant-proof Contact pressure fixture: Stainless steel Filter cell frame: Aluminium Colour – housing: painted to RAL 7035 (light grey) – square visible surface incl. air outlet: painted to RAL 9010 (pure white) or RAL ... Dimensions: Housing LxWxH: ... mm x ... mm x ... mm Filter cell LxBxH: ... mm x ... mm x ... mm Weight with filter cell: ... kg Make: KRANTZ KOMPONENTEN Type: PDV Technische Änderungen vorbehalten! ---------------------------------------------------------------- *1) Available for sizes 1-6 and size up to 1400 m3/h; size 7 > 1400 m3/h corresponds to class H13 ---------------------------------------------------------------- 3.1.2 Tender text Puri inlet, type PEV ... units Puri-inlet, air inlet for filtration of return air from clean rooms directly at the collection point, with perforated plate air inlet for air intake, filter housing air-tight to DIN 25414, including sealing frame for dry sealing with surrounding test groove for tightness test to DIN 1946, Part 4, contact pressure fixture for filter cell, replacement filter cell from below Air connection with __ rectangular connection flange, lateral, __ circular connection spigot, __ lateral, __ on top, Measurement point for pressure differential as well as particle sampling on the untreated air side. HEPA filter cell with cell frame, including dry sealing. Technical data: Volume flow rate: ... l/s (m3/h) Filter class: __ H13; __ H14 *1) Perm. sound power level: ... dB(A) ref. 10-12 W Total pressure loss with uncontaminated filter cell: ... Pa Materials: Filter housing, sealing frame and twist outlet: Galvanized sheet metal Surface protection: Epoxy polyester resin coating, disinfectant-proof Connection housing: Galvanized sheet metal __ Surface protection: Epoxy polyester resin coating, disinfectant-proof Contact pressure fixture: Stainless steel Filter cell frame: Aluminium Colour – housing: painted to RAL 7035 (light grey) – square visible surface incl. air outlet: painted to RAL 9010 (pure white) or RAL ... Dimensions: Housing LxWxH: ... mm x ... mm x ... mm Filter cell LxBxH: ... mm x ... mm x ... mm Weight with filter cell: ... kg Make: KRANTZ KOMPONENTEN Type: PEV Technische Änderungen vorbehalten! ---------------------------------------------------------------- *1) Available for sizes 1-6 and size up to 1400 m3/h; size 7 > 1400 m3/h corresponds to class H13 YIT Germany GmbH KRANTZ KOMPONENTEN Uersfeld 24 | D-52072 Aachen | Germany Phone: +49 241 441-1 | Fax: +49 241 441-555 info@krantz.de | www.krantz.de