1.8. Induction outlet with preset discharge direction IN-N6
For installation flush with ceiling.
Volume flow rate range:
28 – 85 l/(s•m) [100 – 300 m³/(h•m)]
Element width:
90 mm
Standard lengths:
1, 1.2 and 1.6 m
Discharge height:
4 – 7 m
Features:
Stable single jets with alternating inclined discharge, or one-sided single jets at half the volume flow rate, for all ceilings
Fixed discharge angle of 45° to horizontal
With connection box and circular connection spigot
Momentum control device manually adjustable for optimum adjustment of jet momentum to design volume flow rate, or for one-sided air discharge at half volume flow rate