1.1.1. Static cooling ceiling system SKS-4/3, for concealed installation
High-capacity elements for installation above open, suspended ceilings; suitable for cooling all room types and applications but also usable for heating.
Nominal length:
1 000 mm to 4 000 mm
Nominal width:
350 mm to 1 475 mm
Nominal height:
85 mm
Pipe division:
125 mm
Connection type:
push-in fitting, press-fitted connection or solder end
Installation height:
≥ 185 mm, i.e. min. 50 mm gap between concrete ceiling and element
Surface finish:
powder coating to RAL (standard RAL 9005)
Features:
Standard cooling capacity 175 W/m² of cooling element suspended false ceiling (to DIN 4715)
Suitable for high cooling capacities, as required in offices with high heat loads, television studios, technical rooms, or in the industrial sector
Uses the retention capacity of the concrete ceiling
Low temperature differences in the occupied zone
Combinable with any air distribution system
Cooling elements are independent of the false ceiling, so that mechanical installations can be carried out largely separately from ceiling construction
Low installation height saves on building costs and makes this systems particularly suitable for renovation and refitting
The basic element is copper serpentine pipework in one piece, thus no special requirements for chilled water quality; low system costs, long lifetime, assured quality, operating pressure up to 16 bar