1.6.3. Variable twist outlet with guide ring DD-VL
For installation flush with ceiling or downstanding in high halls, particularly suitable for large thermal load fluctuations and high acoustic requirements.
Volume flow rate range:
170 – 2 500 l/s [600 – 9 000 m³/h]
Nominal sizes:
DN 315, DN 400 and DN 630
Discharge height:
3 – 10 m
Features:
Adjustable discharge direction from horizontal to vertical, manually or with servomotor
Radial jet dispersion
Shorter heating-up period with vertical discharge direction